5.9 Adaptation
The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (CO1, 2 -> F11 - 0). The ref
-
erence room, where the room sensor is located, represents the entire building and is moni
-
tored to ensure that the room set point (
Day set point)
is maintained. When to mean mea
-
sured room temperature in rated operation deviates from the adjusted set point, the heating
characteristic is modified accordingly for the following time-of-use. The corrected value is
displayed in parameter levels PA1, 2 under
Gradient, flow
.
Functions
WE Configuration
Room sensors RF1/2 0 CO1, 2 -> F01 - 1
Outdoor sensors AF1/2 1 CO1, 2 -> F02 - 1
Adaptation 0 CO1, 2 -> F08 - 1
4-point characteristic 0 CO1, 2 -> F11 - 0
Parameters
WE Rotary switch / Range of values
Day set point 20 °C Top, middle/0to40°C
Night set point 15 °C Top, middle / 0 to 40 °C
Note!
If the Flash adaptation function is already configured with a small cycle time, the Adaptation
function should not be configured as well.
62 EB 5575 EN
Functions of the heating circuit