9 Memory module
The use of a memory module (accessory no. 1400-7142) is particularly useful to transfer all
data from one TROVIS 5575 Controller to several other TROVIS 5575 Controllers. The mem
-
ory module is plugged into the RJ45 connector integrated into the front panel. Once the
module has been connected, “75 SP“ is displayed. If the memory module already contains
data from a different TROVIS 5575 Controller, turn the rotary pushbutton until “SP 75" is
displayed
4
Pressing the rotary pushbutton to confirm “75 SP“ causes the controller settings to be
transferred to the memory module.
4
Pressing the rotary pushbutton to confirm “SP 75“ causes the saved controller settings to
be transferred from the memory module to the controller.
During the data transfer, the bars on the display indicate the progress. When the transfer
was successful, “I.O.“ is displayed. After that, the connection between controller and mem
-
ory module can be separated.
Using TROVIS-VIEW software (order no. 6661-1011), all of the controller settings can be
configured and archived on a computer.
9.1 Data logging
A data logging module (order no. 1400-9378) saves the following controller data every two
minutes:
4
Temperatures measured by the sensors
4
Control signals [%]
4
Switching states of the pump outputs
4
Access to the controller settings
The data logging module is connected to the RJ-45 jack at the front of the controller. Thanks
to the compact design of the data logging module, the front cover of the controller can be
kept closed even when the module is connected.
The controller starts to write over the oldest data as soon the memory of the data logging
module is full after approximately eight days. The current memory capacity of the data log
-
ging module can be read in the extended operating level under
Info 2
as a second value
(range of values: 0 to 6035). Directly after inserting the data logging module, data can be
first read after the first scanning cycle has been performed.
The data logging viewer software allows the data to be viewed in graph format. The
USB-Converter 3 (order no. 1400-9377) is required to connect the data logging module to a
computer. The data logging viewer software is supplied with the USB-Converter 3.
92 EB 5575 EN
Memory module