Note!
This function is not available when a storage tank thermostat is used.
Controllers that are linked over a device bus are subjected to return flow temperature limita
-
tion in the primary control circuit even during the thermal disinfection in a secondary control
-
ler.
Functions
WE Configuration
Storage sensor SF1 1 CO4 -> F01 - 1
Thermal disinfection 0
3
0:00
4:00
70 °C
10 °C
CO4 -> F14 - 1
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = every day, 1 = Monday, ..., 7 = Sunday
Start time / 0:00h to 23:45h; in steps of 15 minutes
Stop time / 0:00h to 23:45h; in steps of 15 minutes
Disinfection temperature / 60 to 90 °C
Set point boost / 0 to 50 °C
1 bE = 1, 0 (start of disinfection with BE (term. 03/12 =
ON, OFF; only applies when Start time = Stop time)
EB 5575 EN 73
Appendix