EB 6493 EN 7-1
Start-up and conguration at the device
7 Start-up and conguration at the device
The work described in this section is only to be performed by personnel appropriately quali-
ed to carry out such tasks.
Before start-up, make sure the following conditions are met:
The compact controller is properly mounted according to the instructions.
The electrical connection is properly performed.
After applying the supply voltage, the compact controller is ready for use.
Î When potentiometers are used, perform a zero and span calibration (see '-CO- ADJ Cal-
ibration of analog inputs and analog output' in the 'Operation' section).
7.1 Conguration
The controller is congured in the conguration level. In the conguration menu, the control-
ler is adapted to its control task by changing individual conguration items and parameters.
AnnexA contains an overview of all possible settings that can be made. The Conguration
Manual uKH6493 contains detailed descriptions on individual conguration items as well
as other helpful information.
You can enter the conguration data into the conguration protocol (see AnnexA).
Conguration level
You can congure functions and parameters of the compact controller to adapt to a specic
control task. The conguration level has nine menus assigned to functions and their parame-
ters: Each one of the nine menus contains the functions for a certain topic:
PAR: Control parameters
IN: Input
SETP: Set point
CNTR: Controller
OUT: Output
ALRM: Limit relays
AUX: Additional functions
TUNE: Start-up adaptation
I-O: Process data