EB 6493 EN 8-7
Start-up and conguration with TROVIS-VIEW
8.2.3.1 Control parameters [PAR]
The Control parameters [PAR] folder corresponds to the PAR main group of the controller. The
control parameters KP, TN, TV and Y.PRE are set in this folder.
8.2.3.2 Input [IN]
The Input [IN] folder corresponds to the IN main group of the controller. All functions of the
two analog inputs IN1 and IN2 are determined in this folder. The following settings can be
made:
Determining the type of input signal and the measuring range
Signal monitoring
Assigning analog inputs to the controlled variable X or external set point WE
Units
Filtering
Root extraction
Function generation
Assigning units
Units can be assigned to the controlled variable X, the internal set points W/W2 and the ex-
ternal reference variable WE for documentation purposes. The following units can be select-
ed:
°C, degC, degF, K
bar, mbar, psi
kg/s, kg/min, kg/h
l/s, l/min, l/h
m
%
<special>
A user-dened unit can be assigned by selecting '<special>'.
A maximum of 10 characters (a to z, A to Z, 0 to 9, -) are available.