EasyManua.ls Logo

Samson Trovis 6493 - Malfunctions; Troubleshooting

Samson Trovis 6493
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 6493 EN 10-1
Malfunctions
10 Malfunctions
Risk of electric shock while performing electrical connection.
For electrical installation, you are required to observe the relevant electrotechnical regula-
tions of the country of use as well as the regulations of the local power suppliers.
Î Only allow properly trained and qualied personnel to perform the work.
Risk of damage to the compact controller due to incorrectly performed work.
Î Only properly trained personnel appropriately qualied to carry out such tasks must be
allowed to perform corrective action.
10.1 Troubleshooting
When an error occurs, it is indicated on the display and causes the binary output for error
indication to be activated. As soon as an error has been corrected, it is no longer displayed.
The following list contains error messages, possible causes and the recommended action.
We recommend for any errors not described in detail to switch off the supply voltage and to
wait approx. ve seconds before switching it on again.
Table 10-1: Error list · Error messages shown on the device
Error Possible reasons Recommended action
1ERR EEPROM access not possible
Î Return device to SAMSON for repair.2ERR EEPROM cannot be programmed
3ERR Default calibration lost
4ERR Functions changed without user interven-
tion
Î Check the function settings.
5ERR Parameters changed without user interven-
tion
Î Check the parameter settings.
6ERR Position of internal and external set point
unknown
Î Select the external/internal set point.
DANGER
!
NOTICE
!
Tip

Table of Contents

Related product manuals