48
Operating The PM295
name within the group. The setpoint trigger parameters are listed in Table B-7 with
their applicable limits. Table B-8 shows abbreviated labels used for specifying
operate conditions (greater or equal, less or equal, etc.).
NOTE
When the operate or release limit value exceeds the number of places in the
window, the high order digits are expanded to the left window giving a resolution
up to 7 digits. If the value still exceeds the maximum available resolution, it is
converted to higher units (for instance, kW to MW) and a decimal point is placed
in the window to indicate the new measurement range.
To change the setpoint trigger:
Ä From the central window, select the GrP entry with the up/down arrow keys.
Ä Press SELECT to choose the lower window.
Ä Scroll through the applicable trigger groups with the up/down arrow keys until
the desired entry appears.
Ä Press ENTER to return to the central window.
Ä From the central window, select the InP entry with the up/down arrow keys. The
lower window will display the first trigger parameter in the selected group.
Ä Press SELECT to move to the lower window.
Ä Scroll through the applicable triggers with the up/down arrow keys until the
desired entry appears.
Ä Press ENTER to return to the central window.
Ä In the same way, select the Cond entry and specify the operating condition for
the new trigger.
Ä If necessary, check the ConJ entry and fit the type of logical operation to
connect the current trigger to the list of setpoint conditions.
To change operate/release limits for a numeric trigger:
Ä From the central window, select with the up/down arrow keys the On entry to
change operating limit, and the OFF entry to change release limit.
Ä Press SELECT to move to the lower window.
Ä Scroll through the applicable values with the up/down arrow keys until the
desirable value appears.
Ä Press ENTER to return to the central window.