42 GSM-X SATEL
Input / Output / Module / Communication events codes
You can define event codes that will be sent to the monitoring station for events from the
module inputs and outputs and for events related to module and communication. For each
event, you can define codes in three formats:
4/2 [Ademco Express, Sil.Knight/Ademco slow, Radionics 1400Hz, Radionics 1400Hz with
parity] – enter 2 characters (digits or letters from A to F). The event code must be
consistent with the code programmed for the event in the monitoring station.
SIA – select event code consistent with SIA format by using the code editor. To open the
code editor, click on the button.
Contact ID – select event code consistent with CID format by using the code editor. To open
the code editor, click on the button.
7.12 Messaging
The module can send notifications about events by means of:
voice messages – the voice messages which are to be used for notification should be
saved to the module by using the GX Soft program.
SMS/push messages – the content of the messages which are to be used for notification
should be saved to the module by using the GX Soft program.
CLIP – the module provides information about event by calling the programmed phone
numbers and hanging up automatically after maximum 15 seconds. CLIP provides toll-free
messaging capability. The displayed module telephone number should be treated as
a notification of event.
Fig. 36. “Messaging” tab.
Messaging – if this option is enabled, the module can send notifications of module related
events.