INTEGRA SATEL
51
Radio devices – the function makes it possible to check the radio signal level in the ABAX
wireless system devices working in conjunction with the control panel.
Zone Test – the function makes it possible to check the working capacity of zones (detectors
and other devices connected to the zones). The testing may include the burglary and fire
zones. Duration of the test must not exceed 25 minutes. During the test, violation of a zone
can be signaled by sound in the keypad. The test results can be viewed (ÆV
IEW RESULTS
),
and also cleared after completion of the test (ÆC
LEAR RESULTS
). Pressing the X key when
viewing the test results will change the display mode from descriptive to graphic. The
displayed symbols have the following meaning:
- zone was not violated,
O - zone was violated.
Note: Beginning of the zone test in any partition will start the test mode in all ABAX system
wireless devices which are used together with the control panel.
The zone test can be terminated before expiry of the programmed time by using the
F
INISH TEST
command. Maximum 6 seconds can elapse from the moment of giving the
command to the control panel to the actual end of the test (during that time the F
INISH TEST
command will still be visible in the menu).
Manual test transmission – the function generates the event which starts the procedure of
message transmission to the monitoring station (a code sent with the system identifier).
Monitoring station test (1A,1B,2A,2B) – the function makes it possible to carry out the test
transmission to the monitoring station (to each available telephone number separately).
The test transmission is carried out with simultaneously tracking the data transmission
process. Messages on the keypad display indicate the current activity. Practically, this
function is used by the installer when starting communication with a monitoring station.
Messaging test – the function enables carrying out the messaging test. To this effect you
should choose one of the telephone numbers programmed in the control panel and one of
the 16 messages (navigate throughout the function using the T and S keys) and press
the [#] key. If the messaging is working OK, the control panel will call the indicated number
and play back the message.
Answering test – if started when answering the phone call, the function displays information
on the number of rings received by the control panel, and on answered phone call.
Viewing masters – the function is accessible to the master user only. It makes it possible to
check in which objects the master users are created. It allows to control the number of
users who are able to grant permission to access the system in the service mode.
Keypad name – the function shows on display the name of particular keypad (default or
installer assigned).
File in DLOADX – the function displays the date and time of writing the computer data
(DLOADX program) to the control panel, as well as the name of data file.
Panel version – the function shows the current control panel firmware version number on the
keypad display.
IP/MAC ETHM-1 – the function displays the IP address and MAC number of the ETHM-1
module connected to the control panel.
Module versions – the function makes it possible to check the firmware version of the
devices connected to keypad/expander bus.
Note: Not all modules are supported by this function.
Time synchronization – the function is available to the installer or administrator, if the
Ethernet module is connected to the control panel and the time synchronization server has