7
INSTALLATION AND MAINTENANCE
LSA 42.2 - 2 & 4 POLE
ALTERNATORS
3433 en - 2010.10 / g
LEROY-SOMER
3.2.2 - Physical and visual checks
Before starting the machine for the rst time, check that:
- the xing bolts on the feet are tight
- the cooling air is drawn in freely
- the protective louvres and housing are correctly in place
- the standard direction of rotation is clockwise as seen from
the shaft end (phase rotation in order 1 - 2 - 3). For anti-
clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the site operating
voltage (see section § 3.3).
3.3 - Terminal connection diagrams
To modify the connection, change the position of the terminal
cables. The winding code is specied on the nameplate.
Any intervention on the alternator terminals during
reconnection or checks should be performed with
the machine stopped.
Connection codes L.L voltage Factory connection
L1(U)
N
L3(W)
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L2(V)
A
3 phase
3 phase
Winding
60 Hz50 Hz
190 - 208 190 - 240
220 - 230
-
-
190 - 208
6
7
8
N
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L1(U)
L3(W)
L2(V)
D
F
L1(U)
M
L3(W)
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L2(V)
Voltage LM = 1/2 voltage LL
R 250 voltage detection :
0 => (T8) / 110 V => (T11)
R 438 voltage detection :
0 => (T3) / 220 V => (T2)
N
L1(U)
L2(V)
L3(W)
NDE
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
Winding
60 Hz50 Hz
380 - 415 380 - 480
440 - 460
-
-
380 - 416
6
7
8
R 250 voltage detection :
0 => (T8) / 110 V => (T11)
R 438 voltage detection :
0 => (T3) / 380 V => (T2)
NDE
N
L1(U)
L2(V)
L3(W)
L1(U)
L2(V)
L3(W)
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
1 phase
1 phase
or
3 phase
FF
Winding
60 Hz50 Hz
220 - 240 220 - 240
220 - 240
200
250 - 260
-
6
7
8
R 250 voltage detection :
0 => (T1) / 110 V => (T4)
R 438 voltage detection :
0 => (T10) / 220 V => (T1)
NDE
M
L
L
L
L
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
Winding
60 Hz50 Hz
220 - 240 220 - 240
220 - 240
200
250 - 260
-
6
7
8
NDE
T9
T8
T7
T12
T10
T11
T4
T3
T2
T1
T5
T6
L
L
L
T1
T7
T12
T10
T4
T9
T3
T6
T11
T5
T2
T8
L
M
Voltage LM = 1/2 voltage LL
R 250 voltage detection :
0 => (T8) / 110 V => (T11)
R 438 voltage detection :
0 => (T3) / 220 V => (T2)