C.2
SEL-351S Relay Instruction Manual Date Code 20080103
SEL Distributed Port Switch Protocol
Settings
Settings
Use the front-panel {SET} pushbutton or the serial port SET P command to
activate the LMD protocol. Change the port PROTO setting from the default
SEL to LMD to reveal the following settings:
PREFIX: One character to precede the address. This should be a
character that does not occur in the course of other
communications with the relay. Valid choices are one of
the following: “@”, “#”, “$”, “%”, “&”. The default is
“@”.
ADDR: Two-character ASCII address. The range is “01” to “99”.
The default is “01”.
SETTLE: Time in seconds that transmission is delayed after the
request to send (RTS line) asserts. This delay
accommodates transmitters with a slow rise time.