11
Technical data
Processing unit
Operating Instructions – MOVIPRO
®
PHC11A-..M1-..2A-A1/..
101
11.5 Processing unit
General information
Type Micro Dynamic Logic Controller (Micro DLC)
Engineering Engineering is performed via the Ethernet service interface and the Chip-
tool PC software or MOVIVISION
®
.
Digital inputs
Compatibility PLC-compatible according to IEC 61131-2:2008-04 “Standard operating
ranges for digital inputs (current sinking)”
Internal resistance ≈ 3 kΩ
Current consumption ≈ 10 mA
High level DC +13 V – +30 V
Low level DC -3 V – +5 V
Switch-on delay Typ. 250 μs
Deactivation delay Typ. 250 μs
Digital outputs
Compatibility PLC-compatible according to IEC 61131-2:2008-04 “Rated values and op-
erating ranges (DC) for current-sourcing digital DC outputs”
All outputs are short-circuit proof and protected against overload and exter-
nal voltages up to 30 V.
Output current max. DC 500 mA per digital output
Inductive loads Dissipation of inductive switch-off energy up to 0.4 J per output at X5001_1
Dissipation of inductive switch-off energy up to 1 J per output at X5001_2
Freewheeling diodes are not integrated.
Low level DC 0 V
High level DC 24 V
Switch-on delay Typ. 110 μs
Deactivation delay Typ. 110 μs
24 V voltage supply of the buses
Nominal voltage DC 24 V ± 10%
Nominal current Max. DC 500 mA per connection
Output current limiting Max. 2 A (until thermal switch-off)
The continuous output current must not exceed 500 mA.
INFORMATION
The total output power of the 24 V voltage supplies to the plug connectors for buses
and digital inputs/outputs may not exceed 48 W.
20278543/EN – 09/2014