Protective measures against electrical hazards
Operating Instructions – MOVIPRO
®
PHC11A-..M1-..2A-A1/..
43
• Supply system lead 16 mm
2
- 35 mm
2
(AWG 6 – AWG 2):
Route a copper protective earth conductor with a cable cross section of
16 mm
2
.
• Supply system cable > 35 mm
2
(AWG 2):
Route a copper protective earth conductor with half the cross section of the
supply cable.
6.1.3 PE connection for mobile use
For mobile applications, the type of energy transfer determines how to apply ground-
ing or equipotential bonding.
The following energy transfer types can be used:
• Direct power supply, for example via a conductor rail
• Contactless energy transfer system with MOVITRANS
®
Direct power supply
In mobile systems with direct power supply, all electrical equipment such as motor, ap-
plication controller, etc., must be equipped with a ground connection (PE).
Comply with the following rules:
• Ground the unit with the shortest possible route (PE).
• Use a green/yellow grounding cable.
Ground the unit using 2 mobile contact outlets (sliding contacts) or using a trailing ca-
ble.
The following figure shows a sample mobile system with direct power supply via slid-
ing contacts:
MM
L1
L2
L3
PE
[8]
[1]
[2]
[3]
[4]
[5]
[6]
[5]
[2]
[7]
18014398844514443
[1] Stationary system component
[2] Wheels
[3] Vehicle support frame
[4] Power supply
[5] Motor
[6] Application controller
[7] Vehicle GND
[8] Ground
20278543/EN – 09/2014