6
Electrical installation
Protective measures against electrical hazards
Operating Instructions – MOVIPRO
®
PHC11A-..M1-..2A-A1/..
46
6.1.4 Unit connection points for grounding or equipotential bonding
The connection points for grounding or equipotential bonding are marked on the hous-
ing corners of the units with the symbol y.
The bores in the housing corners are prepared for M5 self-tapping screws, for exam-
ple M5 x 12 according to DIN ISO 3506 or equivalent.
Adhere to the following rules when you install the grounding or the equipotential bond-
ing:
Secure the grounding or equipotential bonding cable using connection elements
that breach the surface as shown in the figure below.
Use the grounding kit included in the delivery.
Mount the parts as shown in the figure. Observe the maximum tightening torque of
5 Nm (40 in-lb).
The following figure shows the positions of the connection points and the sequence in
which to install the individual parts:
[1]
[2]
[3]
[4]
[6]
[5]
27021598023672843
[1] Screw, self-tapping
[2] Tooth lock washer
[3] Crimp cable lug for M5
[4] Terminal yoke
[5] Ground symbol y
[6] Housing corner
20278543/EN – 09/2014