Electrical installation
Line connection energy supply
Operating Instructions – MOVIPRO
®
PHC11A-..M1-..2A-A1/..
49
6.2.7 Shielding
Required material
Use shielded power supply and electronics cables.
1. Connect the shield and make sure it is grounded over a wide area at both ends.
2. For cables with multiple shields, also connect the inner shield at both ends making
sure it is grounded over a wide area.
Required documents
For external bus connections, refer to the bus-specific installation instructions.
6.2.8 Unit output
NOTICE
Damage to the unit if the unit output is subjected to capacitive loads.
Damage to the units.
Only connect ohmic/inductive loads.
Never connect capacitive loads.
You may not connect capacitive loads to the unit output. A capacitive load occurs, for
example, when very long cables are used to connect the motor. For this reason, the
incoming motor cable may not exceed 30 m (98 ft).
9007199668673675
20278543/EN – 09/2014