Byte.Bit Description
25.1 Reserved
25.2 ON-delay time (at manual reset)
Default: [0]
[0] disabled
[1] enabled
25.3 ... 25.7 Reserved
26.0 ... 27.7 Startup Delay
Type: INT
Resolution: 0.1 s = 1
Default: 0
Min: 1 or 0 (disabled)
Max: 9999 * 0.1 s = 999.9 s
28.0 ... 29.7 Tripping delay time (if the temperature is overshot or undershot)
Type: INT
Resolution: 0.1 s = 1
Default: 0
Min: 1 or 0 (disabled)
Max: 9999 * 0.1 s = 999.9 s
30.0 ... 31.7 Reserved
32.0 Sensor 1 enabled
Default: [1]
[0] disabled
[1] enabled
32.1 Sensor 2 enabled
Default: [0]
[0] disabled
[1] enabled
32.2 Sensor 3 enabled
Default: [0]
[0] disabled
[1] enabled
32.3 Current input 4...20 mA enabled
Default: [0]
[0] disabled
[1] enabled
32.4 Sensor expansion module / output relay K3
Default: [0]
[0] disabled
[1] enabled
Process data and data sets
16.8 Data set 131 - parameters
3RS2 temperature monitoring relay
Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002 109