Byte.Bit Description
64.1 PIN protection
Default: [0]
[0]: disabled
[1]: enabled
64.2 External comparison measuring point
Default: [0]
[0]: disabled
[1]: enabled
65.0 ... 65.7 Reserved
66.0 ... 67.7 PIN
Type: UINT
Default: 0
Min: 0
Max: 999
Reading always returns 0
68.0 ... 69.7 New PIN
Type: UINT
Default: 0
Min: 0
Max: 999
Reading always returns 0
70.0 ... 70.7 Device mode
Type: BYTE
Default: [0]
[0] standard
[1] ATEX
[2] Temperature monitor TW
[3] Temperature limiter TB
71.0 ... 71.7 Reserved
1) If the unit is mA, this parameter has no e󹪜ect
Process data and data sets
16.8 Data set 131 - parameters
3RS2 temperature monitoring relay
112 Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002