20. HOW TO CONFIGURE A NEW SYSTEM
1. After all of the devices, notification appliances and option modules have been installed, check all wiring
for grounds, shorts and opens.
2. Confirm all wirings are security and switch power on. Panel will recognized all connected devices and
show them under hardware tree. All loop devices are assigned to detection tree and dialer group
automatically. The output devices (i.e., output module, NACs, relays) are assigned to Effect under control
tree automatically.
3. Configure the new system:
Configure Hardware tree: set up a number of overall system parameters, include:
- System relays
- NAC
- Power supply
- Addressable loop
- DACT
- Serial Interface Circuit
Configure Detection tree: set up input zone.
Configure Control tree: set up control logic. The basic concept is that input zones are assigned to
“Cause” as control inputs. The inputs are set to have a certain behavior and activate Effect outputs.
Refer to “How to create/delete logic control”.
Configure Dialer Group: set up dialer group.
4. When finish the setting of a new system, save configure and restart the panel, the new system can run.