EasyManuals Logo

Siemens FC2005 Programming Manual

Siemens FC2005
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Programming Manual of FC2005/FC901
44|63 A6V10333724_b_en_--
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
HFPO-11 Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
Turn Off Bool: True / False (default)
Sensitivity
(SmokeSensor)
Range: 2.45% (default)...3.27%; select an option from the list.
Alarm Verification
(SmokeSensor)
Bool: True / False (default)
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
HMS-S
HMS-D
HMS-M
HMS-2S
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
HTRI-D
HTRI-S
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
HTRI-R Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
Silenceable
(output channel)
Bool: True / False (default)

Other manuals for Siemens FC2005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC2005 and is the answer not in the manual?

Siemens FC2005 Specifications

General IconGeneral
BrandSiemens
ModelFC2005
CategoryControl Panel
LanguageEnglish

Related product manuals