Programming Manual of FC2005/FC901
44|63 A6V10333724_b_en_--
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
HFPO-11 Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
Turn Off Bool: True / False (default)
Sensitivity
(SmokeSensor)
Range: 2.45% (default)...3.27%; select an option from the list.
Alarm Verification
(SmokeSensor)
Bool: True / False (default)
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
HMS-S
HMS-D
HMS-M
HMS-2S
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
HTRI-D
HTRI-S
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
HTRI-R Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50. System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
Silenceable
(output channel)
Bool: True / False (default)