Programming Manual of FC2005/FC901
A6V10333724_b_en_-- 57|63
Turn Off Bool: True / False (default)
Silenceable
(ILED Channel)
Bool: True (default) / False
Silenceable On
Waterflow
(ILED Channel)
Bool: True (default) / False
HoldThroughReset
(ILED Channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
SMS-S
SMS-2S
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
SMS-S/2S:
Manual sensor
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
SFPO-11
SFP-11
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
SFPO-11:
SmokeSensor
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Sensitivity Range: 2.45% (default)...3.27%; select an option from the list.
Alarm Verification Bool: True / False (default)
SFP-11:
SmokeHeatSenso
r
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Sensitivity Range: 2.45% (default)...3.27%
Users can select an option from the list. It is not selectable
when ASD setting is not set to OFF
ASD Setting Set the device application scenario.
Users can choose “off” or select one scenario from the drop
down list.
Alarm Verification Bool: True / False (default)
SFPT-11
(Only available for
ULC type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
SFPT-11:
HeatSensor
Name Name of the device
Name Addition Addition description of the device; max. 20 characters