EasyManuals Logo

Siemens FC2005 Programming Manual

Siemens FC2005
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Programming Manual of FC2005/FC901
56|63 A6V10333724_b_en_--
(SmokeSensor)
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8712
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Enable RateofRise
(HeatSensor)
Bool: True / False (default)
Silenceable
(Output Channel)
Bool: True (default) / False
Silenceable On
Waterflow
(Output Channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(Output Channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8713
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
Turn Off Bool: True / False (default)
ASD Setting
(SmokeHeatSensor)
Set the device application scenario.
Users can choose “off” or select one scenario from the drop
down list.
Sensitivity
(SmokeHeatSensor)
Range: 2.45% (default)...3.27%; select an option from the list.
Available when “ASD Setting” is set to “off”.
Alarm Verification
(SmokeHeatSensor)
Bool: True / False (default)
Available when “ASD Setting” is set to “off”.
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8726
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)

Other manuals for Siemens FC2005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC2005 and is the answer not in the manual?

Siemens FC2005 Specifications

General IconGeneral
BrandSiemens
ModelFC2005
CategoryControl Panel
LanguageEnglish

Related product manuals