Programming Manual of FC2005/FC901
56|63 A6V10333724_b_en_--
(SmokeSensor)
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8712
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Enable RateofRise
(HeatSensor)
Bool: True / False (default)
Silenceable
(Output Channel)
Bool: True (default) / False
Silenceable On
Waterflow
(Output Channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(Output Channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8713
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
Turn Off Bool: True / False (default)
ASD Setting
(SmokeHeatSensor)
Set the device application scenario.
Users can choose “off” or select one scenario from the drop
down list.
Sensitivity
(SmokeHeatSensor)
Range: 2.45% (default)...3.27%; select an option from the list.
Available when “ASD Setting” is set to “off”.
Alarm Verification
(SmokeHeatSensor)
Bool: True / False (default)
Available when “ASD Setting” is set to “off”.
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8726
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50
LED Normal Off Bool: True / False (default)