A6V10333724_b_en_-- 55|63
(Only available for
UL type panel)
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
Silenceable
(output channel)
Bool: True (default) / False
Silenceable On
Waterflow
(output channel)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(output channel)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8705
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Alarm Verification
(Convention)
Bool: True / False (default)
8706
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
Silenceable
(Intelligent Control)
Bool: True (default) / False
Silenceable On
Waterflow
(Intelligent Control)
Available when “Silenceable” (output channel) is set as True.
Bool: True (default) / False
HoldThroughReset
(Intelligent Control)
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8710
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Drift Compensation Bool: True (default) / False
Sensitivity
(SmokeSensor)
Range: 2.45% (default)...3.27%; select an option from the list.
Alarm Verification Bool: True / False (default)