Programming Manual of FC2005/FC901
54|63 A6V10333724_b_en_--
well.
ILED-XC
ILED-XW:
ILED Channel
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Silenceable Bool: True (default) / False
Silenceable On
Waterflow
Bool: True (default) / False
HoldThroughReset
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
ILED-SC
ILED-SW
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
ILED-SC
ILED-SW:
ILED Channel
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Silenceable Bool: True (default) / False
Silenceable On
Waterflow
Bool: True (default) / False
HoldThroughReset
Device won’t be reset when press Reset button on the panel.
Bool: True / False (default)
8700
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
8701
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
8702
8703
(Only available for
UL type panel)
Name Name of the device
Name Addition Addition description of the device; max. 20 characters
Address Range: 1...50; System assigns one address automatically once
a device is added.
LED Normal Off Bool: True / False (default)
Turn Off Bool: True / False (default)
Input Closed
(Input)
Bool: True / False (default)
Normally Open
(Input)
Bool: True (default) / False
8704 Name Name of the device