109/116
Smart Infrastructure Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 24.07.2020
15.7 Manual backup
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
to start a manual backup process.
Parameter PrC appears.
Display: PrC
-
or
+
Press
-
or
+
for parameter bAC.
Display: bAC
nfo
1…3 s
run appears during download (backup process) of the
program sequence.
Alternately
Display shows alternately End and bAC.
Display shows the end of data exchange.
Displa
appears for 2 minutes or can be finished b
pressin
nfo
.
nfo
>1 s
LCD Bild 02/0908
OFF is displayed when the backup process is complete.
Press
nfo
(for > 1 second) to reset the LME7.
Display OFF
Warning!
If any parameters are changed, a backup must be made!
If not observed, there is a risk of impairment of safety functions!