Smart Infrastructure Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 24.07.2020
15.6 Initial startup with a new PME7 or in case of
replacement of the PME7
Alternately
rSt and PrC are displayed alternately.
The replacement of the PME7 is displayed.
The signal lamp lights up alternately, once red and twice
yellow.
nfo
>3 s
Press
nfo
(for >3 seconds) to start data download from the
PME7. The signal lamp flashes yellow. A short flash of the
yellow signal lamp indicates that 3 seconds have passed.
Note:
If you press
nfo
for <3 seconds, data download does not
start. To start the restore process again, the LME7 must be
reset by switching mains ON/OFF.
Display shows run during download (restore process) of the
program sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the LME7 changes to Loc 138
LCD Bild 06/0908
Alternately
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.