13.9 Operating variants of the parameters
The parameters stored in the LME7 can be displayed and changed at parameter level.
SD
AF
>1 s
Press button combination
SD
AF
to display
000: Int.
With
, select the parameter group 100:
PArA.
With
, select the parameter group 200:
PArA.
Pressing the
reset
button takes you to
parameter 226: Preignition time.
13.9.1 Parameters without index, with direct display
13.9.1.1. Example of parameter 225 (prepurge time) on the parameter level
P
Vh
mi n
s%
Bild 166/1107
Press
for prepurge time.
Display: Parameter 225: blinks, value 3.675
does not.
reset
or
P
Vh
mi n
s%
Bild 167/1107
Press
or for editing mode.
Display: 3.675
or
P
Vh
mi n
s%
Bild 168/1107
Press
or to shift the former prepurge
time to change mode one place to the left.
Display: Prepurge time 3.675 blinks.
Note:
To detect display errors, the value appears
one place shifted to the left.
or
P
Vh
mi n
s%
Bild 169/1107
Press
or for the required prepurge
time.
Display: Prepurge time 3.822 blinks.