13 Operation via AZL2 24.07.2020
reset
Press
reset
to activate the restore process.
Display shows run
<3 s
After approx. 3 seconds (depending on the duration of the
program sequence), the displays shows rSt End and
signaled the end of the restore process.
Display: rSt End
It will now be displayed for 2 minutes, or can be finished by pressing the
reset
button
<2
min
or
reset
Display shows OFF when the restore process is finished.
Note
During the restore process, all settings and parameters are written from the PME7 to the
internal memory of the LME7. As part of this process, it is possible that previous program
sequences, parameters, and settings in the internal memory of the LME7 will be overwritten.
Warning!
For initial commissioning or replacement of the PME7, the function sequence and
parameter settings must be checked on completion of the restore process. Failure to
observe this information poses a risk of the safety functions being impaired.
See chapter Operation via AZL2 / first startup, restore
See chapter Operation via internal LED / first startup, restore