EasyManua.ls Logo

Siemens LME71 Series

Siemens LME71 Series
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
111/116
Smart Infrastructure Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 24.07.2020
15.8 Manual restore
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
for starting the manual restore process.
Parameter PrC appears.
Display: PrC
-
or
+
Press
-
or
+
for parameter rSt.
Display: rSt
nfo
1…3 s
run appears during download (restore process) of program
sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the LME7 changes to Loc 138
LCD Bild 06/0908
Alternately
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.
nfo
>1 s
LCD Bild 02/0908
Press
nfo
(for > 1 second) to reset the LME7.
Display OFF

Table of Contents