111/116
Smart Infrastructure Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 24.07.2020
15.8 Manual restore
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
for starting the manual restore process.
Parameter PrC appears.
Display: PrC
-
or
+
Press
-
or
+
for parameter rSt.
Display: rSt
nfo
1…3 s
run appears during download (restore process) of program
sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the LME7 changes to Loc 138
LCD Bild 06/0908
Alternately
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.
nfo
>1 s
LCD Bild 02/0908
Press
nfo
(for > 1 second) to reset the LME7.
Display OFF