15 Operation via internal LED 24.07.2020
Note:
When the program phase (e.g. P10 - shutdown) changes during manual adjustment, the
display blinks
The mode (manual adjustment mode) remains active until ‘Escape’ is used to switch the
LME7 back to normal operation or until the LME7 is reset via mains ON/OFF. This
means that – in the case of a new heat requirement and after startup – the actuator or
the PWM fan is driven to the position or speed of the manually preset value.