Smart Infrastructure Basic Documentation LME7... CC1P7105en
13 Operation via AZL2 24.07.2020
Press
for value 1.
Display: Value 1 blinks
/
reset
Press
/
reset
to activate the backup process.
Display shows run
<3 s
After approx. 3 seconds (depending on the duration of the
program sequence), the displays shows bAC End and
signals the end of the backup process.
Display: bAC End
It will now be displayed for 2 minutes, or can be finished by pressing the
/
reset
button
<2
min
or
/
reset
Display shows OFF when the backup process is finished.
Note
The backup process saves all settings and parameters from the LME7 memory to the PME7.
Warning!
If any parameters are changed, a backup must be made! If this is not observed, there is a
risk of loss of safety functions.