3 Commissioning
MICROMASTER 430 Operating Instructions
38 6SE6400-5AC00-0BP0
3.2.2.1 Commissioning with the BOP-2
You can alter parameter values via the BOP-2. To set parameters on this panel,
you must remove the SDP and attach the BOP-2 (see
Appendix A).
The BOP-2 features a five-digit, seven-segment display
for showing parameter numbers and values, alarm and
fault messages and setpoints and actual values.
Parameter sets cannot be saved via the BOP-2.
Table 3-2 shows the factory default settings for operation
via the BOP-2.
NOTICE
The BOP-2 motor control functions are disabled by default. To control the
motor via the BOP-2, parameter P0700 should be set to 1 and P1000 set to 1.
The BOP-2 can be fitted to and removed from the inverter whilst power is
applied.
If the BOP-2 has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP-2 is removed.
Table 3-2 Default settings for operation using the BOP-2
Parameter Meaning Default Europe (North America)
P0100 Operating Mode Europe/US 50 Hz, kW (60 Hz, hp)
P0307 Power (rated motor) Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
P0310 Motor frequency rating 50 Hz (60 Hz)
P0311 Motor speed rating 1395 (1680) rpm [depending on variant]
P1082 Maximum Motor Frequency 50 Hz (60 Hz)
ATTENTION
MICROMASTER 430 can only be operated using a BOP-2 bedient werden.