6 Troubleshooting
MICROMASTER 430 Operating Instructions
80 6SE6400-5AC00-0BP0
Fault Possible Causes Diagnose & Remedy Reac
tion
F0452
Belt Failure
Detected
Load conditions on motor indicate
belt failure or mechanical fault.
Check the following:
1. No breakage, seizure or obstruction of drive train.
2. If using an external speed sensor, check for
correct function.Check parameters:P0409 (pulse
per min at rated speed).P2191 (Belt failure speed
tolerance).P2192 (delay time for permitted
deviation)
3. If using the torque envelope, check parameters:
P2182 (threshold frequency f1)
P2183 (threshold frequency f2)
P2184 (threshold frequency f3)
P2185 (upper torque threshold 1)
P2186 (lower torque threshold 1)
P2187 (upper torque threshold 2)
P2188 (lower torque threshold 2)
P2189 (upper torque threshold 3)
P2190 (lower torque threshold 3)
P2192 (delay time for permitted deviation)
4. Apply lubrication if required.
Off1
6.4 Alarm messages
Alarm Possible Causes Diagnose & Remedy
A0501
Current Limit
Ø Motor power does not
correspond to the inverter power
Ø Motor leads are too long
Ø Earth faults
Check the following:
1. Motor power (P0307) must correspond to inverter power
(r0206).
2. Cable length limits must not be exceeded.
3. Motor cable and motor must have no short-circuits or
earth faults
4. Motor parameters must match the motor in use
5. Value of stator resistance (P0350) must be correct
6. Motor must not be obstructed or overloaded
Ø Increase the ramp-up-time.
Ø Reduce the boost.
A0502
Overvoltage
limit
Ø Overvoltage limit is reached.
Ø This warning can occur during
ramp down, if the dc-link
controller is disabled (P1240 =
0).
If this warning is displayed permanently, check drive input
voltage .
A0503
UnderVoltage
Limit
Ø Main supply failed
Ø Main supply (P0210) and
consequently DC-link voltage
(R0026) below specified limit
(P2172).
Check main supply voltage (P0210).
A0504
Inverter Over-
Temperature
Warning level of inverter heat-sink
temperature (P0614) is exceeded,
resulting in pulse frequency reduction
and/or output frequency reduction
(depending on parametrization in
(P0610)
Check the following:
1. Ambient temperature must lie within specified limits
2. Load conditions and duty cycle must be appropriate
A0505
Inverter I
2
T
Warning level exceeded, current will
be reduced if parameterized
(P0610 = 1)
Check that duty cycle lies within specified limits