Assembling the panels
110-0084.9 / 15 NXAIR / 40 kA 113
7.13 Switchgear protection IP4X (optional)
Preparations
To achieve the degree of protection IP4X for the switchgear, some components must be sealed with
SIKAFLEX 221-GR 310 ML compound according to the information drawings before final assembly of the
switchgear.
SIKAFLEX 221-GR 310 ML is supplied with the accessories.
For further information, see information drawings NXAIR, order number 110-2300.9.
7.14 Components without installation activity
INFORMATION
Systems assembled and tested at the factory are excluded from installation.
Therefore, do not execute any installation work on:
• Optical sensors for arc detection (optional)
Overpressure monitors for arc detection (optional)
Do not modify or remove any systems assembled and tested at the factory.
Optical sensors (optional)
Depending on its version, the panel may feature a system with optical sensors for arc detection. The system
can cover up to 4 compartments.
The system consists of:
• Control units in the low-voltage compartment
1 optical sensor per covered compartment
• Connecting cables between the control unit and the sensors
Fig. 148: Control units
Fig. 149: Optical sensor (2) and connecting
cable (1), for example in the switching-
device compartment
1
2