Preparing installation
22 NXAIR / 40 kA 110-0084.9 / 15
Fig. 11: Top view of the fixing plate Fig. 12: Front view of the fixing plate
(1)
60
plus 2 mm
(7)
30
plus/minus 1 mm
(2)
50
plus 2 mm
(8)
Plate 80 x 5 x 145 (160) mm,
EN 10025, S235 JR, galvanized
(3)
Plate 30 x 5 x 40 mm,
EN 10025, S235 JR, galvanized
(9)
145
plus/minus 2 mm
(4)
40
plus/minus 1 mm
(10)
30 mm
(5)
30
plus/minus 2 mm
(11)
13 mm
(6)
80
plus/minus 1.5 mm
──
──
The number and arrangement of the necessary foundation rails of the base frame are illustrated in detail in a
dimension drawing. For further information, see information drawings NXAIR, order number 110-2300.9.
5.13 Installation and fixing material with additional earthquake stabilization
Before installing the individual components, the installation and fixing material required has to be prepared.
NOTICE
Vibrations
For panels with additional earthquake stabilization, a welded floor fixing is not
allowed.
Do not apply welded floor fixing on panels with additional earthquake
stabilization.