Preparing installation
22 NXAIR / ≤ 40 kA 110-0084.9 / 15
Fig. 11: Top view of the fixing plate Fig. 12: Front view of the fixing plate
Plate 80 x 5 x 145 (160) mm,
EN 10025, S235 JR, galvanized
Plate 30 x 5 x 40 mm,
EN 10025, S235 JR, galvanized
The number and arrangement of the necessary foundation rails of the base frame are illustrated in detail in a
dimension drawing. For further information, see information drawings NXAIR, order number 110-2300.9.
5.13 Installation and fixing material with additional earthquake stabilization
Before installing the individual components, the installation and fixing material required has to be prepared.
Vibrations
For panels with additional earthquake stabilization, a welded floor fixing is not
allowed.
Do not apply welded floor fixing on panels with additional earthquake
stabilization.