Remove foreign objects, for example:
• Tools
• Unused installation material and cable sections
• Cleaning material
Check the control tightening torques of those bolted joints at random, which
are located at the freely accessible points of the switchgear. They also
include those inside non-bolted compartments:
• Switching-device compartment
• Low-voltage compartment
If it cannot be determined without any doubt that the not freely accessible
bolted joints are properly mounted, make them accessible and check as
well:
• At covered points of the external enclosure
• In the busbar compartment
• In the pressure relief duct
• In the connection compartment
The check of the bolted joints comprises:
Check of the tightening torque with a torque wrench.
If required, correction of the tightening torque according to the above
specifications.