Preparing installation
16 NXAIR / 40 kA 110-0084.9 / 15
5.8 Intermediate storage of the transport units
In original packing as far as possible
Observe permissible storage temperature from −25 °C to +70 °C.
In a weatherproof place
Protected against damage
If packed in seaworthy crates, the switchgear can be stored for a maximum of 6 months (desiccant
bags) at a humidity of max. 60 %
Store transport units in such a way that they can be taken out later in the correct order for installation.
As a rule, the panels should be stored in a closed room. The storage room must have the following
characteristics:
Floor with adequate load-bearing capacity (weights as per delivery note)
Even floor to enable stable storage
Well-ventilated and as free of dust as possible
Dry and protected against humidity and vermin (e.g. insects, mice, rats)
Check humidity in the packing every 4 weeks (condensation)
Do not unpack small parts to avoid corrosion and loss.
If the switchgear or parts thereof are delivered in seaworthy crates, these can be stored up to 6/12 months in
other rooms or outdoors. The storage location must have the following characteristics:
Floor with adequate load-bearing capacity (weights as per delivery note)
Protected against humidity (rain water, flooding, melting water from snow and ice), pollution, vermin
(rats, mice, termites, etc.) and unauthorized access
Place all crates on planks and square timber for protection against floor humidity
After 6 months of storage, have the desiccant agent regenerated professionally. To do this, ask for
expert personnel via the regional Siemens representative.
5.9 Accessories
The following accessories are available:
Racking crank with protective shield for moving the withdrawable part / switching-device truck
Push rod for closing/opening the circuit-breaker mechanically
Hand crank with freewheel for charging the circuit-breaker manually
Operating lever for feeder and busbar earthing switch
Operating lever for the switch-fuse combination
Racking tool for removable voltage transformers
Double-bit key for low-voltage door
Double-bit key for withdrawable part / switching-device truck
Service truck for withdrawable parts
Installation and operating instructions
Craning angle
Slip-on levers for shutter operation (set for left and right side)
Additional service truck for withdrawable parts
Wall-mounting holder for accessories
Earthing accessories (for a panel width of 600 mm and 800 mm)
Plug-in voltage indicator IEC 61243-5/VDE 0682, Part 415, LRM system
for capacitive voltage tap
Test unit for voltage indicator
Coupling unit, 64-pole - 3 m long connection between the withdrawable part / switching-device truck
and the panel for function testing
Tin of Longterm 2 grease (used for contact system, earthing switch blades)
Vaseline (used for busbar and earth connections)
Grease Isoflex TOPAS L32 (used for shutter linkage, guide of withdrawable part /
switching-device truck)
Sealing compound SIKAFLEX 221 (cartridge)
Test equipment for pressure switch
Phase comparison test units
Electrician's ladder (e.g. for operation of the busbar earthing switch)
Craning angles to lift the panel with a crane
Drilling template

Table of Contents

Other manuals for Siemens NXAIR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXAIR and is the answer not in the manual?

Siemens NXAIR Specifications

General IconGeneral
BrandSiemens
ModelNXAIR
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals