Electrical connections
156 NXAIR / 40 kA 110-0084.9 / 15
10.7 Dimensions of three-core cables
The most important dimensions of indoor sealing ends for three-core cables are the permissible length and
diameter of the sealing ends, as well as the length of the cable lug up to and including the heat-shrinkable
splitting cap.
The bolts for the cable sealing ends are already pre-assembled at the cable connection and must not be
changed.
All versions
(except for contactor panel with panel
width 435 mm)
Contactor panel with
panel width 435 mm
U
r
12 kV
U
r
= 17.5 kV
U
r
12 kV
Diameter of
cable sealing end
max. 60 mm
max. 60 mm
max. 60 mm
Length from cable lug
up to and including
heat-shrinkable
splitting cap
max. 500 mm
max. 500 mm
max. 500 mm
Length of cable sealing
end, incl. cable lug
max. 300 mm
max. 300 mm
max. 300 mm
Cable cross-section
max.
240
mm
²
max.
240
mm
²
max.
240
mm
²
Fig. 224: Dimensions of three-core cables
(except for contactor panel with panel
width 435 mm)
Fig. 225: Dimensions of three-core cables in contactor
panel with panel width 435 mm (side view)
(1)
Length of cable sealing end, incl. cable lug
(2)
Length from cable lug up to and including heat-
shrinkable splitting cap
(3)
Diameter of cable sealing end