EasyManua.ls Logo

Siemens NXAIR - Checking the Withdrawable Part on the Service Truck; Checking the Switching-Device Truck; Checking the Service Truck

Siemens NXAIR
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Final assembly work
202 NXAIR / 40 kA 110-0084.9 / 15
Fig. 294: Bushings in switching-device compartment Fig. 295: Detail of bushing
To access the 6 bushings in the switching-device compartment (1), open the shutter to the
connection compartment and the shutter to the busbar compartment, see Operating
Instructions with order number 110-0134.9.
Check the grease film on the silver-plated surface (2) of the fixed contacts in the 6 bushings.
The grease film must be uniformly thin, and applied all around.
If required, clean the silver-plated surface (2) with a soft, lint-free cloth, and grease:
Apply a uniformly thin film of Longterm 2 plus all around.
The surface of the bushing tulips (3) must be clean, dry and non-greasy.
If required, clean with a soft, lint-free cloth.
Check all 6 bushings, and clean if required.
Close the shutter to the connection compartment and the shutter to the busbar
compartment, see Operating Instructions with order number 110-0134.9.
Clean the switching-device compartment.
The 6 bushings in the switching-device compartment are ready for service.
12.10 Checking the withdrawable part on the service truck / checking the switching-device truck
Remove foreign objects.
For cleaning the circuit-breaker, see separate operating instructions for circuit-breaker
3AE.
12.11 Checking the service truck
Remove foreign objects.
Clean the service truck.