EasyManua.ls Logo

Siemens NXAIR - Basic Design Switch-Disconnector Panel

Siemens NXAIR
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unloading and erection
28 NXAIR / 40 kA 110-0084.9 / 15
NOTICE
Damage to the withdrawable part / switching-device truck
The withdrawable part / switching-device truck is an integral part of the transport
unit, and can only be removed after lifting the panel from the wooden pallet and
placing it directly on even firm ground. Normally, this is only the case inside the
switchgear room.
Do not try to remove the withdrawable part / switching-device truck while
the panel is standing on the wooden pallet.
Do not move the service truck in front of the panel if the panel is not standing
directly on the floor.
Observe the instructions on the packing.
Attach ropes, chains, heavy weight slings and comparable means far enough on the hoisting
tackle so that they cannot exert any forces on the panel walls under load.
Use the crane cross-member.
Unload the transport units in packed condition and leave packed for as long as possible.
Do not damage the PE protective foil while unloading.
Set the transport units down as close to the switchgear building as possible in order to avoid
unnecessary ways.
Move the transport units into the building. Only remove packing where absolutely necessary in
order to keep the switchgear as clean as possible.
6.3 Checking for completeness and transport damage
Temporarily open the packing in a weatherproof place, preferably in the building.
Immediately determine and record any damage (and the cause thereof if possible). In case of
transport damage, do this together with the forwarding agent.
If necessary inform the claims agent about the transport damage.
Repair transport damage or have it repaired, otherwise you may not start installation.
Check whether the delivery is complete using the delivery notes and packing lists. If the delivery
is incomplete, inform the regional Siemens representative.
Re-pack the switchgear as far as possible and reasonable. Do not remove the PE foil until
reaching the place of installation in order to keep the switchgear as clean as possible.