Siemens NXAIR - Assembly of Cable Sealing Ends for Single-Core Cables (Except for Contactor Panel with Panel Width 435 MM)

Siemens NXAIR
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connections
110-0084.9 / 15 NXAIR / 40 kA 157
10.8 Assembly of cable sealing ends for single-core cables
(except for contactor panel with panel width 435 mm)
NOTICE
Damage to the switchgear panels
Observe the manufacturer’s information about the tightening torques of the
cable lugs / cable sealing ends.
INFORMATION
Do not attach phase tapes to the cable sealing ends.
Panel versions with up to 2 connection points per phase
In panel versions with 2 connection points per phase, the connection points for cable sealing ends are arranged
one behind the other (viewed from the access to the connection compartment).
Fig. 226: Connection compartment with connections for 2 cables per phase (example)
(1)
Cable connection for 2 cables per phase
(2)
Cable clamp (not supplied)
(3)
Floor plate with rubber sleeve
(4)
Earth connection, connection bolt for earth connection size M12x35
(5)
Cable bracket
1
4
3
5
2