Electrical connections
158 NXAIR / 40 kA 110-0084.9 / 15
Detail view
acc. to Fig. 228:
Panel versions with at least 3 connection points per phase
In panel versions with at least 3 connection points per phase, the connection points for cable sealing ends are
arranged both one behind the other and side by side (viewed from the access to the connection compartment).
NOTICE
Damage to the switchgear panels
Depending on the cable lugs used, the cable lugs of adjacent phases can
be too close to each other. Use only cable lugs keeping the minimum
distance between the cable lugs of adjacent phases.
The panel connections in the connection compartment must all be equipped
with cable sealing ends.
To bolt the cable sealing ends together with the cable connecting lug,
always use the bolting material pre-assembled at the connecting lug.
To coordinate a different procedure, please contact the regional Siemens
representative.
Fig. 227: Connection compartment with connections for 6 cables per phase (example)
(1) cable connection for 6 cables per phase, (2) cable clamp (not supplied),
(3) floor plate with rubber sleeves, (4) earth connection with connection bolt size
M12x35, (5) cable bracket