Accessing the connection compartment through the front
116 NXAIR / 40 kA 110-0084.9 / 15
Procedure
Verify that the position indicator of the feeder earthing switch on the high-voltage door shows
the vertical I position.
Fig. 152: All panel versions except for contactor panels with panel width 435 mm and switch-
disconnector panels: Position indicator of feeder earthing switch on high-voltage
door
Fig. 153: Contactor panels with panel width 435 mm only:
Position indicator of feeder earthing switch on high-voltage door