Accessing the connection compartment through the front
132 NXAIR / ≤ 40 kA 110-0084.9 / 15
Remove the connecting elements from the remaining part of the ventilation duct (4) and the
vertical partition to the connection compartment (5), and store it:
• 13 bolts M8x20 with contact washers and plain washers (6)
• 7 bolts M8x20 with contact washers (7)
Fig. 189: Ventilation duct and partition,
seen from center-right
Fig. 190: Ventilation duct and partition,
seen from center-left
Pull the unit consisting of ventilation duct and vertical partition towards the door threshold as
far as it will go.
To get the unit over the door threshold, lift it approx. 2 cm. Pull it out of the panel. Store the
unit, but do not disassemble the unit any further.
Access to the connection compartment through the panel front is given.