Installation report
216 NXAIR / ≤ 40 kA 110-0084.9 / 15
Position signaling tested for:
"Circuit-breaker spring charged"?
Earthing switch in connection compartment?
Earthing switch in additional compartment to busbar compartment?
Remote control tested for:
Withdrawable part / switching-device truck?
Earthing switch in connection compartment?
Earthing switch in additional compartment to busbar compartment?
Alarm signaling has been tested up to:
Terminal strip in feeder panel?
Digital input/output unit?
Alarm signaling tested for:
Vacuum contactor tripping?
Secondary windings earthed?
Jumpers on current transformer terminal strips in correct position?
Current transformer circuits for measurement tested?
Non-required secondary windings are short-circuited?
Current transformer circuits for protection tested?
Name, Dept., Date:
Primary test of voltage transformers completed?
(test of transformer ratio with e.g. 5 kV)
Voltage transformers earthed on primary side (X, N)?
Secondary test completed?
(test of sense of direction of the secondary winding, e.g. with battery box)
Secondary windings earthed?