Installation report
216 NXAIR / 40 kA 110-0084.9 / 15
7.2
Position signaling tested for:
Circuit-breaker?
"Circuit-breaker spring charged"?
Vacuum contactor?
Earthing switch in connection compartment?
Earthing switch in additional compartment to busbar compartment?
7.3
Remote control tested for:
Circuit-breaker?
Vacuum contactor?
Withdrawable part / switching-device truck?
Earthing switch in connection compartment?
Earthing switch in additional compartment to busbar compartment?
8.
Warning
yes
no
n/a
8.1
Alarm signaling has been tested up to:
Terminal strip in feeder panel?
Transfer terminal strip?
Digital input/output unit?
8.2
Alarm signaling tested for:
MCB trip?
VT MCB trip?
Circuit-breaker trip?
Vacuum contactor tripping?
9.
Current transformers
yes
no
n/a
9.1
Secondary windings earthed?
9.2
Jumpers on current transformer terminal strips in correct position?
9.3
Current transformer circuits for measurement tested?
9.4
Non-required secondary windings are short-circuited?
9.5
Current transformer circuits for protection tested?
Name, Dept., Date:
10.
Voltage transformers
yes
no
n/a
10.1
Primary test of voltage transformers completed?
(test of transformer ratio with e.g. 5 kV)
10.2
Voltage transformers earthed on primary side (X, N)?
10.3
Secondary test completed?
(test of sense of direction of the secondary winding, e.g. with battery box)
10.4
Secondary windings earthed?