Installation report
218 NXAIR / 40 kA 110-0084.9 / 15
NOTICE
Too high test voltage
Excessive test voltages may result in damage to equipment.
Do not perform dielectric test at test voltages exceeding the ratings of the tested equipment.
13.
High-voltage tests acc. to IEC 62271 Part 200 Clause 7.105
yes
no
n/a
High-voltage test performed and reported in attached document?
Annex:
DANGER
Hazardous voltage
After high-voltage test:
Switch off high-voltage test equipment and remove high-voltage test
equipment carefully.
NOTICE
After successful high-voltage testing:
Reset capacitive voltage indicators.
Remove short circuits from current transformers.
Put voltage transformers and surge arresters/limiters back into operation.
Installation report to be submitted after completion via e-mail or normal mail to:
E-mail:
support.energy@siemens.com
Postal
address:
Siemens AG
Global Customer Care AIS-MV
EM MS GCC AIS-MV
Carl-Benz-Straße 22
60386 Frankfurt am Main
Germany
Fax:
+49 69 4008-2623