Unloading and erection
32 NXAIR / ≤ 40 kA 110-0084.9 / 15
Damage to the withdrawable part / switching-device truck
The withdrawable part / switching-device truck is an integral part of the transport
unit, and can only be removed after lifting the panel from the wooden pallet and
placing it directly on even firm ground. Normally, this is only the case inside the
switchgear room.
Do not try to remove the withdrawable part / switching-device truck while
the panel is standing on the wooden pallet.
Do not move the service truck in front of the panel if the panel is not standing
directly on the floor.
The transport units are screwed onto the wooden pallets. If they can no longer be transported together with
the pallets, they are removed as follows:
Lift PE foil about 30 cm.
Undo the screwed angle brackets from the wooden pallet; one each at the front and rear at the
bottom of the panel.
Remove both angle brackets from the panel and then screw the hexagon head bolts again into
the open bolted joints (1) at the front and rear of the panel.
Dispose of the angle brackets.
Additionally for contactor panels with panel width 435 mm: Screw all hexagon head bolts (2)
out of the two transport retainers (3).
Remove
the transport retainers and dispose of them
together with the bolts.
Fig. 23: Circuit-breaker panel
Fig. 24: Contactor panel with panel
width 435 mm
Bolted joints of the angle brackets
Bolted joints of the transport retainers
Left-hand transport retainer (also available on the right as a mirror image)