Assembling the panels
110-0084.9 / 15 NXAIR / ≤ 40 kA 93
Fig. 113: Panels with panel width ≥ 600 mm:
Panel connection links and bolted
joints at the rear
Fig. 114: Contactor panel with panel width
435 mm (center): Panel connection
links and bolted joints at the rear
For further information, see information drawings NXAIR, order number 110-2300.9.
Assembling the busbars in the end panel
The installation of the busbar in the end panel cannot be done from the side. In the upper area of the busbar
compartment, several parts as well as bolts, nuts and washers must be removed.
Foreign objects
Possible malfunctioning and damage to the panels caused by foreign objects.
Before closing panel compartments, remove all foreign objects, e.g.:
• Tools
• Unused installation material
• Packing material
• Cleaning material
Cleaning
Possible malfunctioning and damage to the panels caused by pollution.
Before closing switchgear compartments:
Clean polluted areas. To do this, use a vacuum cleaner and a lint-free cloth.
If necessary, moisten the cloth, use a mild household cleaner, and dry
properly at the end.
Some parts and surfaces of the switchgear are greased for functioning. Do
not remove the grease there; do not clean the parts and surfaces.
If greased areas are dirty, clean the dirty area and grease again according
to the maintenance instructions.