Properties of multiple and single station systems
Property Multiple-station system Single station system
Areas of applica‐
tion
Medium-sized and large systems
Small systems
Local operator stations
Training systems
Configuration Client-server architecture with multiple PCs:
Operator station multiple station system
(Page 22)
BATCH station multiple station system
(Page 24)
Route control station multiple station system
(Page 25)
Maintenance station multiple station system
(Page 25)
One PC for all functions of a
PCS 7 application:
OS single station system (Page 29)
BATCH single station system (Page 32)
Route Control single station system (Page 33)
SIMATIC PCS 7 BOX stations (Page 35)
Maintenance station single station system
(Page 34)
Workstations
Maximum number of clients that a server can
supply with process data: 40
Maximum number of permissible monitors
per server for process mode in a plant: 60
If you operate no more than 4 clients on a
server, you can use a server as an operator
control and monitoring station.
1 workstation with a maximum of 4 monitors (de‐
pending on the application)
Maximum number of monitors that can be connected to a workstation:4 (depending on the hardware
features of the PC)
You can operate the resulting system areas with a single keyboard and mouse.
Availability To guarantee high availability of the PCS 7 plant, you can configure the server as redundant server
pairs (PCs):
Operator station
OS server
MS server
BATCH station
BATCH server
Route Control station
Route Control server
Archive server
Process Historian
You can find additional information on this in the section "Fault-tolerant (redundant) configurations
(Page 15)".
Number of servers Maximum number of servers or server pairs in the PCS 7 plant that can simultaneously access a project
on the OS clients: 18
The following each count as one server:
Server for multiple station systems (see configuration)
Redundant server pair (see configuration)
Archive server
PC components of a PCS 7 system
3.4 Differences between multiple station systems and single station systems