EasyManua.ls Logo

Siemens PGC 302 Edition II - Connection of Valves and Digital Outputs

Siemens PGC 302 Edition II
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection of valves
and digital outputs
The stream selection valves must be connected to the
digital outputs. 24 digital outputs are present on the
terminal board. The first 8 are for internal purposes.
This is shown in the following table.
SIMATIC
- modules are required for further digital out-
puts. To connect these modules, refer in this register to
SIMATIC
modules: Digital outputs or in the register Ex-
ternal wiring diagrams.
CAUTION: Classified area
The solenoid valves must be fused according to
the manufacturers instructions.
Digital
output
Use
+ 24 V means
Terminal on
terminal board
1
2
3
4
5
6
7
8
No device failure (ready)
No maintenance request
Run A
Run B
Cooling on *1
Air flaps moving *1
Air flaps, direction: open *1
Heater enable
30
31
32
33
34
35
36
37
Ground 1 to 8 38
9
10
11
12
13
14
15
16
Available for valves
Available
Available
Available
Available
Available
Available
Available
39
40
41
42
43
44
45
46
Ground 9 to 16 47
17
18
19
20
21
22
23
24
Available
Available
Available
Available
Available
Available
Available
Available for streams
48
49
50
51
52
53
54
55
Ground 17 to 24 56
*1 = Available with PGC 302
N
P
DO 9
39
47
GND
+ 24 V
Connection of valves
0
XK1
9
10
30
39
66
57
48
74
29
19
20
XK1
Installation of chromatograph
8
3INSTALL.CHP, Stand Dezember 22, 1999

Table of Contents