EasyManua.ls Logo

Siemens SCALANCE XC-200 - Page 35

Siemens SCALANCE XC-200
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Configuration and commissioning of the Service Bridge
Service Bridge Setup and Configuration
Entry ID: 109747975, V1.4, 05/2019
35
Siemens AG 2019 All rights reserved
26. Click on the "Add..." button to open the dialog box, where you can add further
IP addresses.
27. Enter an unallocated IP address with the corresponding subnet mask in the
address area of the PROFINET network you want to access, according to your
plant planning (1).
Click on the "Add" button to assign the IP address to the network adapter (2).
1
2
28. Repeat steps 6 and 7 until you have added all the required IP addresses.
Then confirm the open dialogs by clicking the "OK" button to apply the settings.

Other manuals for Siemens SCALANCE XC-200

Related product manuals